[1.8 FAULT MANAGEMENT] (FLt-)<br />

[COM. FAULT MANAGEMENT] (CLL-)<br />

Code<br />

Description<br />

CLL Terminal display: [Network fault mgt]<br />

Logic address: 7015 =16#1B67 Type: WORD (listing)<br />

CANopen index: 2028/10 Read/write: R/WS<br />

INTERBUS index: 5FBC/91 Factory setting: 1<br />

DeviceNet path: 84/01/10<br />

0=[Ignore] (nO): Fault ignored<br />

1=[Freewheel] (YES): Freewheel stop<br />

2=[Per STT] (Stt): Stop according to configuration of [Type of stop] (Stt), see “Stt”, page 194.<br />

4=[fallback spd] (LFF): Change to fallback speed, maintained as long as the fault persists and the run command<br />

has not been removed.<br />

5=[Spd maint.] (rLS): The drive maintains the speed at the time the fault occurred, as long as the fault persists and<br />

the run command has not been removed.<br />

6=[Ramp stop] (rMP): Stop on ramp<br />

7=[Fast stop] (FSt): Fast stop<br />

8=[DC injection] (dCI): DC injection stop<br />

COL Terminal display: [CANopen fault mgt]<br />

Logic address: 7011 =16#1B63 Type: WORD (listing)<br />

CANopen index: 2028/C Read/write: R/WS<br />

INTERBUS index: 5FBC/8D Factory setting: 1<br />

DeviceNet path:<br />

84/01/0C<br />

0=[Ignore] (nO): Fault ignored<br />

1=[Freewheel] (YES): Freewheel stop<br />

2=[Per STT] (Stt): Stop according to configuration of [Type of stop] (Stt), see “Stt”, page 194.<br />

4=[fallback spd] (LFF): Switch to fallback speed, maintained as long as the fault is present and the run command is<br />

not disabled.<br />

5=[Spd maint.] (rLS): The drive maintains the speed at the time the fault occurred, as long as the fault persists and<br />

the run command has not been removed.<br />

6=[Ramp stop] (rMP): Stop on ramp<br />

7=[Fast stop] (FSt): Fast stop<br />

8=[DC injection] (dCI): DC injection stop<br />

SLL Terminal display: [Modbus fault mgt]<br />

Logic address: 7010 =16#1B62 Type: WORD (listing)<br />

CANopen index: 2028/B Read/write: R/WS<br />

INTERBUS index: 5FBC/8C Factory setting: 1<br />

DeviceNet path:<br />

84/01/0B<br />

0=[Ignore] (nO): Fault ignored<br />

1=[Freewheel] (YES): Freewheel stop<br />

2=[Per STT] (Stt): Stop according to configuration of [Type of stop] (Stt), see “Stt”, page 194.<br />

3=[fallback spd] (LFF): Switch to fallback speed, maintained as long as the fault is present and the run command is<br />

not disabled.<br />

4=[Spd maint.] (rLS): The drive maintains the speed at the time the fault occurred, as long as the fault persists and<br />

the run command has not been removed.<br />

5=[Ramp stop] (rMP): Stop on ramp<br />

6=[Fast stop] (FSt): Fast stop<br />

8=[DC injection] (dCI): DC injection stop<br />

241