[1.7 APPLICATION FUNCT.] (FUn-)<br />

Code<br />

Description<br />

rIG Terminal display: [PID integral gain]<br />

Logic address: 11942 = 16#2EA6 Type: UINT<br />

CANopen index: 2059/2B Read/write: R/W<br />

INTERBUS index: 5FBF/5D Unit: 0.01<br />

DeviceNet path: 9C/01/8F Factory setting: 100<br />

Adjustment range: 1 to 10,000<br />

Integral gain<br />

rdG Terminal display: [PID derivative gain]<br />

Logic address: 11943 = 16#2EA7 Type: UINT<br />

CANopen index: 2059/2C Read/write: R/W<br />

INTERBUS index: 5FBF/5E Unit: 0.01<br />

DeviceNet path: 9C/01/90 Factory setting: 0<br />

Adjustment range: 0 to 10,000<br />

Derivative gain<br />

PrP Terminal display: [PID ramp]<br />

Logic address: 11984 = 16#2ED0 Type: UINT<br />

CANopen index: 2059/55 Read/write: R/W<br />

INTERBUS index: 5FBF/67 Unit: 0.1 s<br />

DeviceNet path: 9C/01/B9 Factory setting: 0<br />

Adjustment range: 0 to 999<br />

PID acceleration/deceleration ramp<br />

PIC Terminal display: [PID correct. reverse]<br />

Logic address: 11940 = 16#2EA4 Type: WORD (listing)<br />

CANopen index: 2059/29 Read/write: R/WS<br />

INTERBUS index: 5FBD/0B Factory setting: 0<br />

DeviceNet path:<br />

9C/01/8D<br />

Reversal of the direction of correction<br />

0=[No] (nO)<br />

1=[Yes] (YES)<br />

POL Terminal display: [Min PID output]<br />

Logic address: 11952 = 16#2EB0 Type: INT<br />

CANopen index: 2059/35 Read/write: R/W<br />

INTERBUS index: 5FBF/60 Unit: 0.1 Hz<br />

DeviceNet path: 9C/01/99 Factory setting: 0<br />

Adjustment range:<br />

-5000 to 5000 or -10,000 to<br />

10,000, according to rating<br />

Minimum value of regulator output in Hz<br />