[1.7 APPLICATION FUNCT.] (FUn-)<br />

[FLUXING BY LI] (FLI-)<br />

Code<br />

Description<br />

FLU Terminal display: [Motor fluxing]<br />

Logic address: 13902 = 16#364E Type: WORD (listing)<br />

CANopen index: 206D/3 Read/write: R/W<br />

INTERBUS index: 5FBF/AF Factory setting: 2<br />

DeviceNet path:<br />

A6/01/67<br />

0=[Not cont.] (FnC): Non-continuous mode<br />

1=[Continuous] (FCt): Continuous mode<br />

2=[No] (FnO): Function inactive<br />

FLI Terminal display: [Fluxing assignment]<br />

Logic address: 13901 = 16#364D Type: WORD (listing)<br />

CANopen index: 206D/2 Read/write: R/WS<br />

INTERBUS index: 5FBD/5D Factory setting: 0<br />

DeviceNet path:<br />

A6/01/66<br />

0=[No] (nO): Not assigned<br />

129 = [LI1] (LI1)<br />

:<br />

142 = [LI14] (LI14)<br />

160 = [CD00] (Cd00)<br />

:<br />

175 = [CD15] (Cd15)<br />

177 = [C101] (C101)<br />

:<br />

239 = [C415] (C415)<br />

See: “Assignment conditions for logic inputs and control bits”, page 181.<br />