[1.8 FAULT MANAGEMENT] (FLt-)<br />

[DB RES. PROTECTION] (brP-)<br />

Code<br />

Description<br />

brO Terminal display: [DB res. protection]<br />

Logic address: 14111 = 16#371F Type: WORD (listing)<br />

CANopen index: 206F/C Read/write: R/WS<br />

INTERBUS index: 5FBD/60 Factory setting: 0<br />

DeviceNet path:<br />

A7/01/70<br />

0=[No] (nO): No braking resistor protection (thereby preventing access to the other function parameters)<br />

1=[Alarm] (ALrM): The alarm may be assigned to a logic output or a relay, see “r1”, page 168.<br />

2=[Fault] (FLt): Switch to fault (bOF) with locking of drive (freewheel stop).<br />

brP Terminal display: [DB Resistor Power]<br />

Logic address: 14112 = 16#3720 Type: UINT<br />

CANopen index: 206F/D Read/write: R/W<br />

INTERBUS index: 5FBD/<strong>61</strong> Unit: 0.11 kW<br />

DeviceNet path: A7/01/71 Factory setting: 1<br />

Rated power of the resistor used<br />

brU Terminal display: [DB Resistor value]<br />

Adjustment range: 1 to 10,000<br />

Logic address: 14113 = 16#3721 Type: UINT<br />

CANopen index: 206F/E Read/write: R/W<br />

INTERBUS index: 5FBD/62 Unit: 0.11 Ω<br />

DeviceNet path: A7/01/72 Factory setting: 1<br />

Rated value of the braking resistor in Ohms<br />

Adjustment range: 1 to 2000<br />