Priority stops<br />

DSP402 profile<br />

In DSP402 profile, separate or not separate mode:<br />

Stop and fault commands configured for fixed assignment (LIpp, C1pp, C2pp, C3pp, C4pp) to terminal inputs or control word bits are<br />

priority commands, even if the channel is not active.<br />

Commands configured for switched assignment (Cd11 ... Cd15) are active only if the channel is active.<br />

Fixed assignments are configured using the following values:<br />

Cp11 is assigned by default to the reverse command [Reverse assign.] (rrS).<br />

On the terminal:<br />

Channel<br />

Run on state command<br />

[2 wire] (2C)<br />

(1) If assignment is fixed, value required for starting, even if another channel is active.<br />

Run on edge command<br />

[3 wire] (3C)<br />

Drive terminal LI2 ... LI6 LI3 ... LI6<br />

Logic I/O card<br />

LI7 ... LI10<br />

Extended I/O card<br />

LI11 ... LI14<br />

Integrated Modbus<br />

C111 ... C115<br />

CANopen<br />

C211 ... C215<br />

Communication card<br />

C311 ... C315<br />

"Controller Inside" card<br />

C411 ... C415<br />

Command Configuration = 0 = 1<br />

Value for<br />

starting (1)<br />

State reached since<br />

5-Operation enabled<br />

Freewheel stop<br />

[Freewheel stop ass.]<br />

(nSt)<br />

stop no stop 1 2-Switch on disabled<br />

Fast stop [Fast stop assign.] (FSt) stop no stop 1 4-Switched on<br />

DC injection braking<br />

[DC injection assign.]<br />

(dCI)<br />

no braking braking 0 5-Operation enabled<br />

External fault [External fault ass.] (EtF) no fault fault 0 8-Fault<br />

In the case of a run on edge command, configured via [3 wire] (3C), the stop command (run enable) is assigned by default to LI1. This<br />

command is active even if the terminal is not the active channel.<br />

Via the network:<br />

Command Configuration = 0 = 1<br />

Value for<br />

starting (1)<br />

State reached since<br />

5-Operation enabled<br />

Fast stop [Fast stop assign.] (FSt) no stop stop 0 4-Switched on<br />

DC injection braking<br />

[DC injection assign.]<br />

(dCI)<br />

no braking braking 0 5-Operation enabled<br />

External fault [External fault ass.] (EtF) no fault fault 0 8-Fault<br />

(1) If assignment is fixed, value required for starting, even if another channel is active.<br />

In DSP402 profile, it is not possible to assign the freewheel stop command [Freewheel stop ass.] (nSt) to the control word. Freewheel stop<br />

is achieved using the "5-Disable operation" or "Halt" commands with the type of stop [Type of stop] (Stt) parameter configured as<br />