[1.8 FAULT MANAGEMENT] (FLt-)<br />

[UNDERVOLTAGE MGT] (USb-)<br />

Code<br />

Description<br />

USb Terminal display: [UnderV. fault mgt]<br />

Logic address: 13803 =16#35EB Type: WORD (listing)<br />

CANopen index: 206C/4 Read/write: R/WS<br />

INTERBUS index: 5FBD/58 Factory setting: 0<br />

DeviceNet path:<br />

A6/01/04<br />

0=[Flt&R1open] (0): Fault and fault relay open.<br />

1=[Flt&R1close] (1): Fault and fault relay closed.<br />

2=[Alarm] (2): Alarm and fault relay remains closed. The alarm may be assigned to a logic output or a relay.<br />

UrES Terminal display: [Evacuation Input V.]<br />

Logic address: 13801 =16#35E9 Type: WORD (listing)<br />

CANopen index: 206C/2 Read/write: R/WS<br />

INTERBUS index: 5FBD/56 Factory setting: According to drive rating<br />

DeviceNet path:<br />

A6/01/02<br />

Rated voltage of the line supply in V.<br />

20 = [200] (200): 200 V<br />

22 = [220] (220): 220 V<br />

24 = [240] (240): 240 V<br />

26 = [260] (260): 260 V<br />

38 = [380] (380): 380 V<br />

40 = [400] (400): 400 V<br />

44 = [440] (440): 440 V<br />

46 = [460] (460): 460 V<br />

48 = [480] (480): 480 V<br />

USL Terminal display: [Undervoltage level]<br />

Logic address: 13802 =16#35EA Type: UINT<br />

CANopen index: 206C/3 Read/write: R/WS<br />

INTERBUS index: 5FBD/57 Unit: 1V<br />

DeviceNet path:<br />

A6/01/03<br />

Undervoltage fault trip level setting in V. The adjustment range and factory setting are determined by the drive rating and the<br />

value of [Evacuation Input V.] (UrES).<br />

USt Terminal display: [Undervolt. time out]<br />

Logic address: 13804 =16#35EC Type: UINT<br />

CANopen index: 206C/5 Read/write: R/WS<br />

INTERBUS index: 5FBD/59 Unit: 0.11 s<br />

DeviceNet path: A6/01/05 Factory setting: 2<br />

Time delay for taking undervoltage fault into account<br />

Adjustment range: 2 to 9999<br />