[1.5 INPUTS / OUTPUTS CFG] (I-O-)<br />

[AI3 CONFIGURATION] (AI3-)<br />

Code<br />

Description<br />

AI3t Terminal display: [AI3 Type]<br />

Logic address: 4404 = 16#1134 Type: WORD (listing)<br />

CANopen index: 200E/5 Read/write: R<br />

INTERBUS index: 5FBC/36 Factory setting: 2<br />

DeviceNet path: 77/01/05<br />

2=[Current] (0A): Current input<br />

CrL3 Terminal display: [AI3 min value]<br />

Logic address: 4434 = 16#1152 Type: UINT<br />

CANopen index: 200E/23 Read/write: R/WS<br />

INTERBUS index: 5FBC/3F Unit: 0.1 mA<br />

DeviceNet path: 77/01/23 Factory setting: 0<br />

Adjustment range:<br />

0to200<br />

CrH3 Terminal display: [AI3 max value]<br />

Logic address: 4444 = 16#115C Type: UINT<br />

CANopen index: 200E/2D Read/write: R/WS<br />

INTERBUS index: 5FBC/42 Unit: 0.1 mA<br />

DeviceNet path: 77/01/2D Factory setting: 200<br />

Adjustment range:<br />

0to200<br />

AI3F Terminal display: [AI3 filter]<br />

Logic address: 4454 = 16#1166 Type: UINT<br />

CANopen index: 200E/37 Read/write: R/WS<br />

INTERBUS index: 5FBC/46 Unit: 0.01 s<br />

DeviceNet path: 77/01/37 Factory setting: 0<br />

Interference filtering<br />

AI3L Terminal display: [AI3 range]<br />

Adjustment range: 0 to 1000<br />

Logic address: 4484 = 16#1184 Type: WORD (listing)<br />

CANopen index: 200E/55 Read/write: R/WS<br />

INTERBUS index: 5FBC/51 Factory setting: 0<br />

DeviceNet path: 77/01/55<br />

0=[0 - 100%] (POS): Unidirectional input<br />

1=[+/- 100%] (nEG): Bidirectional input<br />