[1.7 APPLICATION FUNCT.] (FUn-)<br />

[STOP CONFIGURATION] (Stt-)<br />

Code<br />

Description<br />

Stt Terminal display: [Stop type]<br />

Logic address: 11201 = 16#2BC1 Type: WORD (listing)<br />

CANopen index: 2052/2 Read/write: R/WS<br />

INTERBUS index: 5FBC/F2 Factory setting: 0<br />

DeviceNet path: 99/01/02<br />

Stop mode on disappearance of the run command or appearance of a stop command.<br />

0=[Ramp stop] (rMP): On ramp<br />

1=[Fast stop] (FSt): Fast stop<br />

2=[Freewheel] (nSt): Freewheel stop<br />

3=[DC injection] (dCI): DC injection stop<br />

nSt Terminal display: [Freewheel stop ass.]<br />

Logic address: 11202 = 16#2BC2 Type: WORD (listing)<br />

CANopen index: 2052/3 Read/write: R/WS<br />

INTERBUS index: 5FBC/F3 Factory setting: 0<br />

DeviceNet path: 99/01/03<br />

0=[No] (nO): Not assigned<br />

129 = [LI1] (LI1)<br />

:<br />

142 = [LI14] (LI14)<br />

In I/O profile only:<br />

160 = [CD00] (Cd00)<br />

:<br />

175 = [CD15] (Cd15)<br />

177 = [C101] (C101)<br />

:<br />

239 = [C415] (C415)<br />

See: “Assignment conditions for logic inputs and control bits”, page 181.<br />

FSt Terminal display: [Fast stop assign.]<br />

Logic address: 11204 = 16#2BC4 Type: WORD (listing)<br />

CANopen index: 2052/5 Read/write: R/WS<br />

INTERBUS index: 5FBC/F5 Factory setting: 0<br />

DeviceNet path: 99/01/05<br />

0=[No] (nO): Not assigned<br />

129 = [LI1] (LI1)<br />

:<br />

142 = [LI14] (LI14)<br />

160 = [CD00] (Cd00)<br />

:<br />

175 = [CD15] (Cd15)<br />

177 = [C101] (C101)<br />

:<br />

239 = [C415] (C415)<br />

See: “Assignment conditions for logic inputs and control bits”, page 181.<br />