[1.7 APPLICATION FUNCT.] (FUn-)<br />

[OUTPUT CONTACTOR CMD] (OCC-)<br />

Code<br />

Description<br />

OCC Terminal display: [Out. contactor ass.]<br />

Logic address: 13104 = 16#3330 Type: WORD (listing)<br />

CANopen index: 2065/5 Read/write: R/WS<br />

INTERBUS index: 5FBD/3D Factory setting: 0<br />

DeviceNet path:<br />

A2/01/69<br />

Logic output or control relay<br />

0=[No] (nO): Function not assigned (in this case, none of the function parameters can be accessed)<br />

129 = [LO1] (LO1): Logic output (if one or two I/O cards have been inserted, LO1 to LO2 or LO4 can be selected)<br />

130 = [LO2] (LO2)<br />

131 = [LO3] (LO3)<br />

132 = [LO4] (LO4)<br />

146 = [R2] (r2): Relay (selection of R2 extended to R3 or R4 if one or two I/O cards have been inserted)<br />

147 = [R3] (r3)<br />

148 = [R4] (r4)<br />

rCA Terminal display: [Output contact. fdbk]<br />

Logic address: 13103 = 16#332F Type: WORD (listing)<br />

CANopen index: 2065/4 Read/write: R/WS<br />

INTERBUS index: 5FBD/3C Factory setting: 0<br />

DeviceNet path:<br />

A2/01/68<br />

0=[No] (nO): Not assigned<br />

129 = [LI1] (LI1)<br />

:<br />

142 = [LI14] (LI14)<br />

160 = [CD00] (Cd00)<br />

:<br />

175 = [CD15] (Cd15)<br />

177 = [C101] (C101)<br />

:<br />

239 = [C415] (C415)<br />

See: “Assignment conditions for logic inputs and control bits”, page 181.<br />

The motor starts up when the assigned input or bit changes to 0.<br />

dbS Terminal display: [Time to motor run]<br />

Logic address: 13101 = 16#332D Type: UINT<br />

CANopen index: 2065/2 Read/write: R/W<br />

INTERBUS index: 5FBF/A6 Unit: 0.01 s<br />

DeviceNet path: A2/01/66 Factory setting: 15<br />

Time delay for:<br />

• Motor control following the sending of a run command<br />

• Output contactor fault monitoring, if the feedback is assigned<br />

Adjustment range: 5 to 6000<br />