[1.8 FAULT MANAGEMENT] (FLt-)<br />

[MOTOR THERMAL PROT.] (tHt-)<br />

Code<br />

Description<br />

tHt Terminal display: [Motor protect. type]<br />

Logic address: 9<strong>61</strong>2 = 16#258C Type: WORD (listing)<br />

CANopen index: 2042/D Read/write: R/WS<br />

INTERBUS index: 5FC2/09 Factory setting: 1<br />

DeviceNet path:<br />

91/01/0D<br />

0=[No active] (nO): No protection<br />

1=[Self cooled] (ACL): For self-cooled motors<br />

2=[Force-cool] (FCL): For force-cooled motors<br />

ttd Terminal display: [Motor therm. level]<br />

Logic address: 11002 = 16#2AFA Type: UINT<br />

CANopen index: 2050/3 Read/write: R/W<br />

INTERBUS index: 5FBF/33 Unit 1%<br />

DeviceNet path: 98/01/03 Factory setting: 100<br />

Adjustment range<br />

0to118<br />

Trip threshold for motor thermal alarm (logic output or relay)<br />

ttd2 Terminal display: [Motor2 therm. level]<br />

Logic address: 11006 = 16#2AFE Type: UINT<br />

CANopen index: 2050/7 Read/write: R/W<br />

INTERBUS index: 5FBF/36 Unit 1%<br />

DeviceNet path: 98/01/07 Factory setting: 100<br />

Adjustment range<br />

0to118<br />

Trip threshold for motor thermal alarm (logic output or relay)<br />

ttd3 Terminal display: [Motor3 therm. level]<br />

Logic address: 11007 = 16#2AFF Type: UINT<br />

CANopen index: 2050/8 Read/write: R/W<br />

INTERBUS index: 5FBF/37 Unit 1%<br />

DeviceNet path: 98/01/08 Factory setting: 100<br />

Adjustment range<br />

0to118<br />

Trip threshold for motor thermal alarm (logic output or relay)<br />