[1.8 FAULT MANAGEMENT] (FLt-)<br />

[TORQUE OR I LIM. DETECT.] (tId-)<br />

Code<br />

Description<br />

SSb Terminal display: [Trq/I limit. stop]<br />

Logic address: 9240 =16#2418 Type: WORD (listing)<br />

CANopen index: 203E/29 Read/write: R/WS<br />

INTERBUS index: 5FBC/B9 Factory setting: 0<br />

DeviceNet path:<br />

8F/01/29<br />

0=[Ignore] (nO): Fault ignored<br />

1=[Freewheel] (YES): Freewheel stop<br />

2=[Per STT] (Stt): Stop according to configuration of [Type of stop] (Stt), see “Stt”, page 194.<br />

4=[fallback spd] (LFF): Change to fallback speed, maintained as long as the fault persists and the run command<br />

has not been removed.<br />

5=[Spd maint.] (rLS): The drive maintains the speed at the time the fault occurred, as long as the fault persists and<br />

the run command has not been removed.<br />

6=[Ramp stop] (rMP): Stop on ramp<br />

7=[Fast stop] (FSt): Fast stop<br />

8=[DC injection] (dCI): DC injection stop<br />

StO Terminal display: [Trq/I limit. time out]<br />

Logic address: 9241 =16#2419 Type: UINT<br />

CANopen index: 203E/2A Read/write: R/W<br />

INTERBUS index: 5FBF/2C Unit: 1ms<br />

DeviceNet path: 8F/01/2A Factory setting: 1000<br />

Time delay for taking SSF "Limitation" fault into account<br />

Adjustment range: 0 to 9999<br />