Setpoint parameters<br />

See section “Assignment of setpoints from a network”, page 55<br />

Code<br />

Description<br />

LFRD Parameter name: Speed reference<br />

DSP402 name:<br />

DRIVECOM name:<br />

vl target velocity<br />

Speed-Setpoint<br />

Logic address: 8602 = 16#219A Type: INT<br />

CANopen index: 6042 Read/write: R/W<br />

INTERBUS index: 6042 Unit: rpm<br />

DeviceNet path:<br />

2A/01/08 (1)<br />

8C/01/03 (2)<br />

Parameter conforming to DSP402 and ODVA profiles.<br />

Signed value.<br />

LFR Parameter name: Frequency reference<br />

Terminal display:<br />

[Frequency ref.]<br />

Logic address: 8502 = 16#2136 Type: INT<br />

CANopen index: 2037/3 Read/write: R/W<br />

INTERBUS index: 5FB6/1C Unit: 0.1 Hz or standardized<br />

DeviceNet path:<br />

8B/01/67<br />

16 signed bits based on the<br />

maximum frequency (TFR)<br />

Signed value.<br />

The unit depends on the value of bit 9 of the extended control word:<br />

= 0: 0.1 Hz<br />

= 1: Standardized value on 16 signed bits at maximum frequency. The value 32767 corresponds to [Max frequency]<br />

(tFr). The default value of [Max frequency] (tFr) is 60 Hz, and the resolution is then approximately 0.0018 Hz.<br />

PISP Parameter name: PID regulator reference<br />

Logic address: 8503 = 16#2137 Type: INT<br />

CANopen index: 2037/4 Read/write: R/W<br />

INTERBUS index: 5FB6/1D Unit: 1<br />

DeviceNet path:<br />

8B/01/68<br />

Signed value.<br />

If the PID regulator is to be controlled via a network, this reference must be written, in accordance with the protocol:<br />

• Either via messaging<br />

• Or by assigning this parameter in the periodic variables<br />

AIU1 Parameter name: PID regulator feedback<br />

Logic address: 5281 = 16#14A1 Type: INT<br />

CANopen index: 2016/52 Read/write: R/W<br />

INTERBUS index: 5FB9/43 Unit: 1<br />

DeviceNet path:<br />

7B/01/52<br />

MFr Parameter name: Multiplying coefficient<br />

Terminal display:<br />

[Multiplying coeff.]<br />

Logic address: 11831 = 16#2E37 Type: UINT<br />

CANopen index: 2058/20 Read/write: R/W<br />

INTERBUS index: 5FB6/38 Unit: 1%<br />

DeviceNet path:<br />

9C/01/20<br />

(1) path standard ODVA. It can be used for explicit messaging. Do not use for the assignment of an assembly.<br />

(2) path <strong>Altivar</strong>. Avoid using for explicit messaging if you want to garantee future interchangeability. Use This path for the assignment in<br />

an assembly.<br />