Log parameters<br />

Code<br />

Description<br />

ULP8 Parameter name: Supply voltage on fault n-8<br />

Logic address: 7278 = 16#1C6E Type: UINT<br />

CANopen index: 202A/4F Read/write: R<br />

INTERBUS index: 5FB9/A0 Unit: 0.1 V<br />

DeviceNet path:<br />

85/01/4F<br />

LCP8 Parameter name: Motor current on fault n-8<br />

Logic address: 7248 = 16#1C50 Type: INT<br />

CANopen index: 202A/31 Read/write: R<br />

INTERBUS index: 5FB9/85 Unit: 0.1 A<br />

DeviceNet path: 85/01/31<br />

rFP8 Parameter name: Output frequency on fault n-8<br />

Logic address: 7258 = 16#1C5A Type: INT<br />

CANopen index: 202A/3B Read/write: R<br />

INTERBUS index: 5FB9/8E Unit: 0.1 Hz<br />

DeviceNet path:<br />

85/01/3B<br />

tHP8 Parameter name: Motor thermal state on fault n-8<br />

Logic address: 7288 = 16#1C78 Type: UINT<br />

CANopen index: 202A/59 Read/write: R<br />

INTERBUS index: 5FB9/A9 Unit: 1<br />

85/01/59 85/01/59<br />

EP8 Parameter name: Status word on fault n-8<br />

Logic address: 7218 = 16#1C32 Type: WORD (bit register)<br />

CANopen index: 202A/13 Read/write: R<br />

INTERBUS index: 5FB9/6A Unit: -<br />

DeviceNet path: 85/01/13<br />

IP8 Parameter name: Extended status word on fault n-8<br />

Logic address: 7228 = 16#1C3C Type: WORD (bit register)<br />

CANopen index: 202A/1D Read/write: R<br />

INTERBUS index: 5FB9/73 Unit: -<br />

DeviceNet path:<br />

85/01/1D<br />

CMP8 Parameter name: Command word on fault n-8<br />

Logic address: 7238 = 16#1C46 Type: WORD (bit register)<br />

CANopen index: 202A/27 Read/write: R<br />

INTERBUS index: 5FB9/7C Unit: -<br />

DeviceNet path: 85/01/27<br />