[1.8 FAULT MANAGEMENT] (FLt-)<br />

[4-20mA LOSS] (LFL-)<br />

Code<br />

Description<br />

LFL2 Terminal display: [AI2 4-20mA loss]<br />

Logic address: 7003 =16#1B5B Type: WORD (listing)<br />

CANopen index: 2028/4 Read/write: R/WS<br />

INTERBUS index: 5FBC/87 Factory setting: 0<br />

DeviceNet path: 84/01/04<br />

0=[Ignore] (nO): Fault ignored. This configuration is the only one possible if [AI2 min. value] (CrL2), see “CrL2”,<br />

page 1<strong>61</strong>, is not greater than 3 mA.<br />

1=[Freewheel] (YES): Freewheel stop<br />

2=[Per STT] (Stt): Stop according to configuration of [Type of stop] (Stt), see “Stt”, page 194.<br />

4=[fallback spd] (LFF): Change to fallback speed, maintained as long as the fault persists and the run command<br />

has not been removed.<br />

5=[Spd maint.] (rLS): The drive maintains the speed at the time the fault occurred, as long as the fault persists and<br />

the run command has not been removed.<br />

6=[Ramp stop] (rMP): Stop on ramp<br />

7=[Fast stop] (FSt): Fast stop<br />

8=[DC injection] (dCI): DC injection stop<br />

LFL3 Terminal display: [AI3 4-20mA loss]<br />

Logic address: 7013 =16#1B65 Type: WORD (listing)<br />

CANopen index: 2028/E Read/write: R/WS<br />

INTERBUS index: 5FBC/8F Factory setting: 0<br />

DeviceNet path:<br />

84/01/0E<br />

0=[Ignore] (nO): Fault ignored. This configuration is the only one possible if [AI3 min. value] (CrL3), see “CrL3”,<br />

page 163, is not greater than 3 mA.<br />

1=[Freewheel] (YES): Freewheel stop<br />

2=[Per STT] (Stt): Stop according to configuration of [Type of stop] (Stt), see “Stt”, page 194.<br />

4=[fallback spd] (LFF): Change to fallback speed, maintained as long as the fault persists and the run command<br />

has not been removed.<br />

5=[Spd maint.] (rLS): The drive maintains the speed at the time the fault occurred, as long as the fault persists and<br />

the run command has not been removed.<br />

6=[Ramp stop] (rMP): Stop on ramp<br />

7=[Fast stop] (FSt): Fast stop<br />

8=[DC injection] (dCI): DC injection stop<br />

LFL4 Terminal display: [AI4 4-20mA loss]<br />

Logic address: 7014 =16#1B66 Type: WORD (listing)<br />

CANopen index: 2028/F Read/write: R/WS<br />

INTERBUS index: 5FBC/90 Factory setting: 0<br />

DeviceNet path:<br />

84/01/0F<br />

0=[Ignore] (nO): Fault ignored. This configuration is the only one possible if [AI4 min. value] (CrL4), see “CrL4”,<br />

page 165, is not greater than 3 mA.<br />

1=[Freewheel] (YES): Freewheel stop<br />

2=[Per STT] (Stt): Stop according to configuration of [Type of stop] (Stt), see “Stt”, page 194.<br />

4=[fallback spd] (LFF): Change to fallback speed, maintained as long as the fault persists and the run command<br />

has not been removed.<br />

5=[Spd maint.] (rLS): The drive maintains the speed at the time the fault occurred, as long as the fault persists and<br />

the run command has not been removed.<br />

6=[Ramp stop] (rMP): Stop on ramp<br />

7=[Fast stop] (FSt): Fast stop<br />

8=[DC injection] (dCI): DC injection stop<br />