[1.4 MOTOR CONTROL] (drC-)<br />

Code<br />

Description<br />

bFr Terminal display: [Standard mot. freq]<br />

Logic address: 3015 = 16#BC7 Type: WORD (listing)<br />

CANopen index: 2000/10 Read/write: R/WS<br />

INTERBUS index: 5FBC/05 Factory setting: 0<br />

DeviceNet path: 70/01/10<br />

0=[50 Hz] (50): IEC<br />

1=[60 Hz] (60): NEMA<br />

This parameter modifies the presets of the following parameters: [High speed] (HSP), see “HSP”, page 139, [Freq.<br />

threshold] (Ftd), see “Ftd”, page 141, [Rated motor volt.] (UnS), see below, [Rated motor freq.] (FrS), see “FrS”,<br />

page 143 and [Max frequency] (tFr), see “tFr”, page 143.<br />

nPr Terminal display: [Rated motor power]<br />

Logic address: 9<strong>61</strong>3 = 16#258D Type: UINT<br />

CANopen index: 2042/E Read/write: R/WS<br />

INTERBUS index: 5FC2/0A Unit: According to drive rating and<br />

bFr (1)<br />

DeviceNet path: 91/01/0E Factory setting: According to drive rating<br />

Rated motor power given on the nameplate.<br />

UnS Terminal display: [Rated motor volt.]<br />

Adjustment range:<br />

Logic address: 9601 = 16#2581 Type: UINT<br />

CANopen index: 2042/2 Read/write: R/WS<br />

INTERBUS index: 5FC2/01 Unit: 1V<br />

DeviceNet path: 91/01/02 (2)<br />

28/01/07 (3)<br />

Rated motor voltage given on the nameplate.<br />

nCr Terminal display: [Rated mot. current]<br />

Factory setting:<br />

According to drive rating<br />

According to drive rating and<br />

bFr<br />

Adjustment range: According to drive rating (4)<br />

Logic address: 9603 = 16#2583 Type: UINT<br />

CANopen index: 2042/4 Read/write: R/WS<br />

INTERBUS index: 5FC2/03 Unit: 0.1 A<br />

DeviceNet path: 91/01/04<br />

28/01/06<br />

(2)<br />

(3)<br />

Rated motor current given on the nameplate.<br />

Factory setting:<br />

According to drive rating<br />

Adjustment range: 0.25 In to 1.5 In (5)<br />

(1) According to drive rating and bFr<br />

If bFr = 0 and if power > 75 kW: Unit = 1 kW<br />

If bFr = 0 and if power ≤ 75 kW: Unit = 0.01 kW<br />

If bFr = 1: Unit = 0.1 HP (75 W) regardless of power<br />

(2)<br />

Path standard ODVA. It can be used for explicit messaging. Do not use for the assignment of an assembly.<br />

(3)<br />

Path <strong>Altivar</strong>. Avoid using for explicit messaging if you want to garantee future interchangeability. Use This path for the assignment in<br />

an assembly.<br />

(4) According to drive voltage<br />

ATV<strong>61</strong>pppM3X: Adjustment range = 100 to 240<br />

ATV<strong>61</strong>pppN4: Adjustment range = 200 to 480<br />

(5) In corresponds to the rated drive current indicated in the installation manual and on the drive nameplate.<br />