<strong>2704</strong> Controller Programmer Operation<br />

6.8.3. To Apply Holdback<br />

To apply holdback (see also 6.3.8) to each segment of the program or to the overall program,<br />

follow this procedure:-<br />

Do This<br />

1. Select PROGRAM EDIT<br />

(Program Page)<br />

This Is The Display You<br />

Should See<br />

Additional Notes<br />

This is fully described in<br />

6.7.1.<br />

2. Press to show the list<br />

of parameters<br />

3. Press to choose<br />

‘HBk Mode’<br />

4. Press to select ‘HBk<br />

Mode’<br />

5. Press or to<br />

choose Per Program (or<br />

Per Segment)<br />

This parameter only<br />

appears if Holdback has<br />

been configured.<br />

If per program is chosen<br />

the next parameter is<br />

‘HBk Type’.<br />

If per segment is chosen<br />

the parameter ‘HBk Type’<br />

does not appear.<br />

For HBk Mode = per program.<br />

6. Press to select PSP1<br />

HBk Type<br />

7. Press or to<br />

choose the type eg Fine<br />

Lo<br />

The choices are:-<br />

Off; Fine Lo; Fine Hi; Fine<br />

B<strong>and</strong>; Coarse Lo: Coarse<br />

Hi; Coarse B<strong>and</strong>.<br />

If HBk Type ≠ Off, the<br />

next parameter allows the<br />

holdback value to be set<br />

up.<br />

Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00 6-29