Transducer Scaling<br />

<strong>2704</strong> Controller<br />

19.2.1. To Calibrate a Strain Gauge Bridge Transducer<br />

The <strong>controller</strong> must have been configured for Cal Type = Shunt, <strong>and</strong> the transducer<br />

connected as shown in Figure 2-13 using the ‘Transducer Power Supply’. Then:-<br />

Do This<br />

This Is The Display You<br />

Should See<br />

It is first necessary to enable calibration as follows:-<br />

Additional Notes<br />

1. From any display press<br />

as many times as necessary<br />

to access the page header<br />

menu<br />

2. Press or to select<br />

‘TXDCR SCALING’<br />

3. Press to show Subheaders<br />

4. Press or to select<br />

‘Txdcr 1’ (or 2 or 3)<br />

The choices are :<br />

Txdcr 1<br />

Txdcr 2<br />

Txdcr 3<br />

This text can be user<br />

defined<br />

5. Press to show the<br />

parameter list<br />

6. Press again to select<br />

Enable Cal<br />

7. Press or to On<br />

This parameter remains<br />

‘On’ once it has been set.<br />

It requires to be switched<br />

‘Off’ manually.<br />

It may be wired to an<br />

external digital input<br />

source such as a key<br />

switch<br />

19-4 Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr -00