Technical Specification<br />

<strong>2704</strong> Controller<br />

C. Appendix C Technical Specification<br />

All figures quoted at 0 to 50 o C unless otherwise stated.<br />

C.1.<br />

Sample rate<br />

Input filtering<br />

User calibration<br />

Sensor break<br />

Thermocouple<br />

types<br />

General<br />

ALL ANALOGUE, DUAL AND PV INPUTS<br />

9Hz (110msec.)<br />

OFF to 999.9 seconds of filter time constant (f.t.c.). Default setting is<br />

0.4 seconds unless stated otherwise<br />

Both the user calibration <strong>and</strong> a transducer scaling can be applied.<br />

a.c. sensor break on each input (i.e. fast responding <strong>and</strong> no dc errors<br />

with high impedance sources).<br />

Most linearisations including K,J,T,R,B,S,N,L,PII,C,D,E with<br />

linearisation error < ±0.2°C<br />

Resolution (noise free) is quoted as a typical figure with f.t.c. set to the<br />

default value = 0.4 second.<br />

Resolution generally improves by a factor of two with every<br />

quadrupling of f.t.c.<br />

Calibration is quoted as offset error + percentage error of absolute<br />

reading at ambient temperature of 25 O C<br />

Drift is quoted as extra offset <strong>and</strong> absolute reading errors per degree of<br />

ambient change from 25 O C.<br />

C-2 Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 2.0 Apr-00