<strong>2704</strong> Controller Installation<br />

2.4. OPTIONAL PLUG IN MODULE CONNECTIONS<br />

2.4.1. Digital Communications Connections<br />

Digital Communications modules can be fitted in two positions in the <strong>2704</strong> <strong>controller</strong>, (see<br />

also section 1.5). The connections being available on HA to HF <strong>and</strong> JA to JF depending on<br />

the position in which the module is fitted. The two positions could be used, for example, to<br />

communicate with ‘iTools’ configuration package on one position, <strong>and</strong> to a PC running a<br />

supervisory package on the second position.<br />

The connections shown in the following diagrams show RS232, 2-wire RS485, 4-wire RS422<br />

<strong>and</strong> master/slave comms to a second <strong>controller</strong>.<br />

The diagrams show connections for ‘bench top test’ wiring. For a full description of the<br />

<strong>installation</strong> of a communications link, including line resistors, see Communications<br />

H<strong>and</strong>book, Part No. HA026230, <strong>and</strong> EMC Installation Guide, part no. HA025464.<br />

RS232<br />

PC<br />

HA<br />

HB<br />

Rx<br />

Tx<br />

Com<br />

HC<br />

HD<br />

Common<br />

HE<br />

Rx<br />

HF<br />

Tx<br />

Figure 2-10: RS232 Communications Connections<br />

RS285 - 2 wire<br />

PC<br />

Connections ‘daisy<br />

chained’ to other<br />

instruments<br />

HA<br />

HB<br />

RS232 to<br />

RS485<br />

2-wire<br />

converter<br />

Rx Tx Com<br />

RxB TxB<br />

RxA Com TxA<br />

HC<br />

HD<br />

HE<br />

HF<br />

Common<br />

A(+)<br />

B(-)<br />

Figure 2-11: RS485 2- Wire Communications Connections<br />