<strong>2704</strong> Controller Transducer Scaling<br />

19.4.1. To Calibrate a Controller Against a Second Reference<br />

Do This<br />

This Is The Display You<br />

Should See<br />

Additional Notes<br />

Enable calibration as described in steps 1-7 of section 19.2.1.<br />

Then allow the process to settle at the low calibration point<br />

8. Press as many times<br />

as necessary to scroll to<br />

‘Start Pnt1 Cal’<br />

9. Press or to ‘On’<br />

This parameter can be<br />

configured to be activated<br />

from a digital input <strong>and</strong><br />

wired, for example, to an<br />

external switch. If this<br />

has been configured this<br />

parameter can be turned<br />

on from this source.<br />

10. Press as many times<br />

as necessary to scroll to<br />

‘Adjust Value’<br />

11. Press or to enter<br />

the value indicated on the<br />

reference instrument<br />

12. Press to confirm or<br />

to cancel as<br />

instructed<br />

The confirm message<br />

does not appear unless<br />

‘Adjust Value’ is changed.<br />

If the displayed value is<br />

acceptable change it<br />

momentarily then back to<br />

the value to step to the<br />

next stage.<br />

On confirm the current<br />

input value is stored as<br />

‘Input Low’ <strong>and</strong> the value<br />

entered by the user is<br />

stored in the ‘Scale Low’<br />

parameter.<br />

Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00 19-9