Tuning<br />

<strong>2704</strong> Controller<br />

8.5.2. Integral action <strong>and</strong> manual reset<br />

In a full three-term <strong>controller</strong> (that is, a PID <strong>controller</strong>), the integral term automatically<br />

removes steady state errors from the setpoint. If the <strong>controller</strong> is set up to work in two-term<br />

mode (that is, PD mode), the integral term will be set to ‘OFF’. Under these conditions the<br />

measured value may not settle precisely at setpoint. When the integral term is set to ‘OFF’<br />

the parameter manual reset appears in the Loop Setup (PID) page. This parameter represents<br />

the value of the power output that will be delivered when the error is zero. You must set this<br />

value manually in order to remove the steady state error.<br />

8.5.3. To Manually Set PID Values<br />

See Section 9.2 ‘To Set Up PID Parameters ‘.<br />

8.5.4. Valve Position Control<br />

See section 9.7 ‘Control of Valve Positioning Motors’, for an explanation of the additional<br />

parameters required for motorised valves <strong>and</strong> how to set the values of these parameters.<br />

8-10 Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00