<strong>2704</strong> Controller Module IO<br />

18.3.11. Dual PV Input<br />

The dual PV input module accepts two inputs - one from a high level source (channel A) <strong>and</strong><br />

one from a low level source (channel C). The two inputs are not isolated from each other <strong>and</strong><br />

have an update rate of 5Hz. A typical application for the module is for a zirconia probe input.<br />

The module can also be configured for a single input when the update rate becomes 10Hz.<br />

Table Number:<br />

18.3.11.<br />

This page allows you to set the parameters for<br />

Channel A of a Dual PV Input module.<br />

This module can only be fitted in slots 3 or 6.<br />

MODULE IO<br />

(Module 3(A)<br />

Page)<br />

Parameter Name Parameter Description Value Default Access<br />

Level<br />

This module has two inputs. Parameters are displayed under ‘channel’ (A) <strong>and</strong> ‘channel’ (C)<br />

Channel A is the high level input, channel C is the low level input. This table shows Module<br />

3 (or 6)A parameters<br />

Ident High Level Input R/O<br />

Electrical Lo Electrical low input level Input range L3.<br />

Electrical Hi Electrical high input level units as<br />

configured<br />

Eng Value Lo Low display reading Display range ‘To<br />

Scale<br />

Eng Value Hi High display reading Display range the PV<br />

Input’<br />

Filter Time Input filter time Off to<br />

0:10:00.0<br />

L3<br />

Electrical Val<br />

Module 3A Val<br />

The current electrical<br />

value of the input<br />

The current value in<br />

engineering units.<br />

Module 3A can be a user<br />

defined name.<br />

Input range units<br />

as configured<br />

Offset Transducer scale offset Range limits<br />

Module Status Module status OK<br />

Initialising<br />

Ch A Sbreak<br />

Ch A OutRange<br />

Ch A IP Sat<br />

Ch A Not Calib<br />

SBrk Trip Imp<br />

Current sensor break<br />

value<br />

Read as a % of the SBrk<br />

Impedance configured<br />

See<br />

R/O<br />

R/O<br />

R/O<br />

R/O<br />

Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00 18-13