<strong>2704</strong> Controller Input Operators<br />

11.2.3. Compensation for Sensor Non-Linearities<br />

The custom linearisation feature can also be used to compensate for errors in the sensor or<br />

measurement system. The intermediate points are, therefore, available in Level 1 so that<br />

known discontinuities in the curve can be calibrated out. Figure 11.2 shows an example of<br />

the type of discontinuity which can occur in the linearisation of a temperature sensor.<br />

Output Hi<br />

eg 1000 o C<br />

Cal Point 6<br />

Output 2( to 15)<br />

Cal Point 5<br />

Cal Point 4<br />

Cal Point 3<br />

Cal Point 2<br />

Cal Point 1<br />

Output Lo<br />

eg 0 o C<br />

Input Lo<br />

eg 0 o C<br />

Input 2( to 15)<br />

Input Hi<br />

eg 1000 o C<br />

Figure 11-2: Compensation for Sensor Discontinuities<br />

The calibration of the sensor uses the same procedure as described above. Adjust the output<br />

(displayed) value against the corresponding input value to compensate for any errors in the<br />

st<strong>and</strong>ard linearisation of the sensor.<br />

Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00 11-7