Loop Set Up<br />

<strong>2704</strong> Controller<br />

9.5.3. Setpoint Tracking<br />

When the control loop is placed in manual or ratio has been deselected, setpoint tracking can<br />

be used to recalculate the actual achieved ratio, thereby ensuring bumpless transfer between<br />

modes. If the input from the lead process value at any time becomes invalid, then the<br />

working setpoint of the loop will remain at its current value<br />

9.5.4. Ratio Control Parameters LP1 SETUP (Ratio Page)<br />

Table Number:<br />

9.5.4.<br />

This list allows you to set up parameters<br />

specific to ratio <strong>controller</strong>s<br />

LP1 SETUP<br />

(Ratio Page)<br />

Parameter Name Parameter Description Value Default Access<br />

Level<br />

Lead PV<br />

The value of the lead<br />

process variable<br />

L1<br />

Measured Ratio Measured Ratio R/O<br />

Ratio WSP Ratio working setpoint R/O<br />

Ratio Lo Lim Ratio setpoint low limit L3<br />

Ratio Hi Lim Ratio setpoint high limit L3<br />

Ratio SP Ratio setpoint L1<br />

Enable Ratio Ratio enable No<br />

Yes<br />

Ratio Trim Ratio trim value L1<br />

L1<br />

9-12 Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00