05.06.2015 Views

model 2704 controller installation and operation handbook - Soliton

model 2704 controller installation and operation handbook - Soliton

model 2704 controller installation and operation handbook - Soliton

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>2704</strong> Controller Loop Set Up<br />

9.8. OUTPUT PARAMETERS<br />

Table Number:<br />

9.8.<br />

This list allows you to set up the parameters<br />

which control the control output to the plant<br />

LP1 SETUP<br />

(Output Page)<br />

Parameter Name Parameter Description Value Default Access<br />

Level<br />

Loop Mode<br />

OP Low Limit<br />

OP High Limit<br />

OP Rate Limit<br />

On/Off control output only.<br />

Allows the <strong>controller</strong> to be<br />

switched into manual<br />

Sets a low limit on an<br />

analogue output signal<br />

Sets a high limit on an<br />

analogue output signal<br />

Sets the rate at which the<br />

output value changes<br />

Auto<br />

Manual<br />

-100% to<br />

100%<br />

-100% to<br />

100%<br />

Off to<br />

99.99<br />

%/sec<br />

OP Rate Lim En Output rate limit enable Off<br />

On<br />

Forced OP<br />

SBrk OP<br />

CH1 OP<br />

Ch1 Hysteresis<br />

Sets the output value when<br />

the <strong>controller</strong> is switched to<br />

manual - alternative to<br />

bumpless transfer<br />

Sets the level of the output<br />

under sensor break<br />

conditions<br />

Reads the current value of<br />

channel 1 output<br />

Only shown if the output<br />

relay 1 is configured as<br />

on/off. It sets the difference<br />

between relay on <strong>and</strong> relay<br />

off.<br />

Ch1 Min Pulse Output minimum on time<br />

(on/off control)<br />

The above three parameters are repeated for channel 2<br />

Deadb<strong>and</strong><br />

Deadb<strong>and</strong> between ch1 <strong>and</strong><br />

ch2 - only applies if both ch1<br />

<strong>and</strong> ch2 are configured<br />

-100% to<br />

100%<br />

-100% to<br />

100%<br />

-100% to<br />

100%<br />

Off to<br />

9999.9<br />

Off to<br />

100.0<br />

Target OP Target output power -100 to<br />

100%<br />

Rem Lo OP Lim Remote low power limit -100% to<br />

100%<br />

Rem Hi OP Lim Remote high power limit -100% to<br />

100%<br />

Auto<br />

Off<br />

L1<br />

L3<br />

L3<br />

L3<br />

L3<br />

L3<br />

L3<br />

R/O<br />

L3<br />

L3<br />

L1<br />

L3<br />

L3<br />

Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00 9-17

Hooray! Your file is uploaded and ready to be published.

Saved successfully!