Alarm Operation<br />

<strong>2704</strong> Controller<br />

7.2.6. Rate Of Change Alarm (Negative Direction)<br />

The Process Value falls faster than the alarm setting.<br />

↑<br />

PV<br />

Alarm On<br />

Alarm Off<br />

Negative<br />

Rate of<br />

Change set<br />

to x units per<br />

Actual rate of<br />

change > x<br />

units per min<br />

↓<br />

↑<br />

Hysteresis<br />

Time<br />

→<br />

7.2.7. Rate Of Change Alarm (Positive Direction)<br />

The Process Value rises faster than the alarm setting.<br />

↑<br />

PV<br />

Alarm On<br />

Alarm Off<br />

Actual rate of<br />

change > x<br />

units per min<br />

↓<br />

Hysteresis<br />

↑<br />

Positive Rate<br />

of Change<br />

set to x units<br />

per min<br />

Time<br />

→<br />

Notes:<br />

1. Separate alarms are required for positive <strong>and</strong> negative rates of change<br />

2. An alarm is indicated during the period that the actual rate of change is greater than the<br />

set rate of change.<br />

3. There may be a small delay before the instrument displays an alarm condition since the<br />

instrument requires several samples. This delay increases if the set value <strong>and</strong> actual value<br />

are close together<br />

4. A hysteresis value of, say, 1 unit per second will prevent the alarm from ‘chattering’ if<br />

the rate of change varies by this amount<br />

7-6 Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00