05.06.2015 Views

model 2704 controller installation and operation handbook - Soliton

model 2704 controller installation and operation handbook - Soliton

model 2704 controller installation and operation handbook - Soliton

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Loop Set Up<br />

<strong>2704</strong> Controller<br />

Master<br />

PV<br />

Master PID<br />

Loop<br />

Csd Trim<br />

Lim<br />

Master<br />

SP<br />

Master<br />

OP<br />

Remote<br />

Input<br />

Csd FF<br />

Value<br />

Feedforward<br />

Selection<br />

Slave<br />

PV<br />

Slave PID<br />

Loop<br />

Control<br />

Output<br />

Figure 9-1: Cascade with Feedforward<br />

9.4.5. Cascade Parameters LP1 SETUP (Cascade Page)<br />

Table Number:<br />

9.4.5.<br />

This list allows you to set up<br />

parameters specific to cascade<br />

<strong>controller</strong>s<br />

LP1 SETUP<br />

(Cascade Page)<br />

Parameter Name Parameter Description Value Default Access<br />

Level<br />

Disable CSD Cascade disable status Off<br />

On<br />

CSD FF Value<br />

CSD FF Trim Lim<br />

Master OP<br />

Cascade feedforward value<br />

i.e. The value being fed<br />

forward<br />

Cascade feedforward trim<br />

limit i.e. The amount the<br />

master output can be<br />

trimmed up <strong>and</strong> down.<br />

Cascade master PID output<br />

power<br />

Range of<br />

signal<br />

being fed<br />

forward<br />

Range of<br />

slave loop<br />

Range of<br />

slave loop<br />

L1<br />

L3<br />

L3<br />

R/O<br />

9-10 Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00