<strong>2704</strong> Controller Alarm Operation<br />

7.7. ALARM ACKNOWLEDGEMENT<br />

A new alarm can be acknowledged in four ways:<br />

1. By pressing <strong>and</strong> simultaneously<br />

2. From an external source, such as a pushbutton, connected to a suitably configured digital<br />

input<br />

3. Through digital communications<br />

The message will remain on the screen <strong>and</strong> the alarm symbol, , will continue to flash until<br />

the alarm is acknowledged - you are prompted to do this by pressing <strong>and</strong><br />

simultaneously. The symbol will stop flashing <strong>and</strong> remain illuminated until all alarm<br />

conditions are removed. If a further alarm occurs the symbol will start flashing again <strong>and</strong> a<br />

new alarm message will pop up.<br />

The message displayed indicates the source of the alarm <strong>and</strong> may be customised to the users<br />

terminology. The source will inherit the name of the channel or the loop or the user alarm<br />

name.<br />

The <strong>operation</strong> of the alarm acknowledgement depends whether the alarm is non-latching or<br />

latching, auto or manual reset. This is shown in the following tables:-<br />

Non Latched Alarms<br />

Alarm<br />

Condition<br />

Acknowledge Symbol Message Ext relay<br />

(if fitted)<br />

ON No Flashing Alarm message On<br />

Off No Off Former display Off<br />

Alarm<br />

Condition<br />

Acknowledge Symbol Alarm message Ext relay<br />

(if fitted)<br />

ON No Flashing Alarm message On<br />

On Yes Steady Former display Off<br />

Off Off Former message Off<br />

Latched Alarm - Auto<br />

Alarm<br />

Condition<br />

Acknowledge Symbol Message Ext relay<br />

(if fitted)<br />

ON No Flashing Alarm message On<br />

Off No Flashing Alarm message On<br />

Off<br />

Yes<br />

Alarm<br />

Condition<br />

Acknowledge Symbol Message Ext relay<br />

(if fitted)<br />

ON No Flashing Alarm message On<br />

ON Yes Steady °:Access Level Off<br />

Off - Off Normal display Off<br />

Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00 7-15