<strong>2704</strong> Controller Transducer Scaling<br />

19.3.1. To Calibrate a Load Cell<br />

Do This<br />

This Is The Display You<br />

Should See<br />

Additional Notes<br />

Enable calibration as described in steps 1-7 of section 19.2.1.<br />

Then set the load cell to its ‘zeroed’ condition<br />

1. Press as many times<br />

as necessary to scroll to<br />

‘Start Pnt1 Cal’<br />

2. Press or to ‘On’<br />

This parameter can be<br />

configured so that it is<br />

activated from a digital<br />

input <strong>and</strong> wired, for<br />

example, to an external<br />

switch. If this has been<br />

configured this parameter<br />

can be turned on from<br />

this source.<br />

During the time taken for<br />

the <strong>controller</strong> to calculate<br />

the low point calibration<br />

value, the Cal Active<br />

parameter will be On.<br />

When the Calibration low procedure is complete, place the reference load on the load<br />

cell<br />

3. Press to scroll to<br />

Start Pnt2 Cal<br />

4. Press or to On<br />

It can be configured to be<br />

initiated from a digital<br />

input <strong>and</strong> wired, for<br />

example, to an external<br />

switch. If this has been<br />

configured this parameter<br />

can be turned on from<br />

this source.<br />

The <strong>controller</strong> must have been configured for Cal Type = Load Cell, <strong>and</strong> the transducer<br />

connected as shown in Chapter 2. Then:-<br />

Note:-<br />

‘Scale High’ is the high calibration point <strong>and</strong> ‘Scale Low’ is the low calibration point. These<br />

should be set to the range over which calibration is required. ‘Threshold Value’ applies as in<br />

the previous section.<br />

Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00 19-7