<strong>2704</strong> Controller Tuning<br />

Typical automatic tuning cycle<br />

PV<br />

Setpoint<br />

Calculation of the cutback values<br />

Low cutback <strong>and</strong> High cutback are values that restrict the amount of overshoot, or<br />

undershoot, that occurs during large step changes in PV (for example, under start-up<br />

conditions).<br />

If either low cutback, or high cutback, is set to ‘Auto’ the values are fixed at three times the<br />

proportional b<strong>and</strong>, <strong>and</strong> are not changed during automatic tuning.<br />

Time<br />

8.4. CASCADE TUNING<br />

In the <strong>2704</strong> <strong>controller</strong> a cascade loop can be tuned using the autotune feature.<br />

The cascade autotuner tunes to the local setpoint of the auxiliary loop. This value should be<br />

set to the value at which the process is typically operated. For example, for a furnace<br />

typically used around 1000 o C, set ‘Local SP’ (Aux) to 1000 o C. The autotune will take place<br />

at a level below this to ensure that the process operating conditions are not exceeded.<br />

Similarly, since autotune applies the full range of the output signal to the process it may in<br />

some cases be desirable to limit this range to protect the process.<br />

Cascade autotune tunes the slave loop first followed by the master. For a more detailed<br />

description of cascade autotune or tuning of cascade loops manually, see the <strong>2704</strong><br />

Engineering H<strong>and</strong>book, Part No. HA026933.<br />

8.4.1. Automatic Tuning of a Cascade Loop<br />

1. On the loop overview page, set ‘Local SP’ to the value at which the process typically<br />

operates. Alternatively, this value can also be set in the LPx SETUP (SP(Aux)) page.<br />

2. Set ‘Tune OL’ <strong>and</strong> ‘Tune OH’ (if necessary) to the required limits for the process.<br />

These parameters can be found in the AUTOTUNE page.<br />

3. From the AUTOTUNE page header, choose the parameter ‘Autotune Loop’ <strong>and</strong> select<br />

‘LPx (CSD)’.<br />

Cascade control is described in Chapter 9<br />

Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00 8-5