Tuning<br />

<strong>2704</strong> Controller<br />

8.3. TO AUTOTUNE CONTOL LOOP LP1<br />

In most cases it will only be necessary to carry out the Autotune procedure when<br />

commissioning your <strong>controller</strong>.<br />

Do This<br />

This Is The Display You<br />

Should See<br />

Additional Notes<br />

Set the setpoint to the value at which you will normally operate the process .<br />

1. From any display press<br />

as many times as<br />

necessary to access the<br />

page header menu<br />

Autotune page is at Level 3<br />

by default, but may have<br />

been promoted to L1 or L2.<br />

2. Press or to<br />

select ‘AUTOTUNE’<br />

3. Press to display<br />

sub-headers<br />

4. Press or to<br />

select ‘Autotune Loop’<br />

5. Press to select the<br />

parameter.<br />

The choices are:-<br />

LP1<br />

LP1A<br />

LP1 Cascade<br />

These are repeated for<br />

Loops 2 <strong>and</strong> 3<br />

Note:<br />

Text shown in italics is user<br />

definable in configuration<br />

mode <strong>and</strong> may be different<br />

from that shown<br />

6. Press or to<br />

choose the loop to tune<br />

1. The <strong>controller</strong> induces an oscillation in the PV by first turning the output (power) on, <strong>and</strong><br />

then off. The first cycle is not complete until the measured value has reached the required<br />

setpoint.<br />

2. After two cycles of oscillation the tuning is completed <strong>and</strong> the tuner switches itself off.<br />

3. When the <strong>controller</strong> is autotuning the status of autotune is shown periodically on the<br />

relevant loop summary<br />

4. The <strong>controller</strong> then calculates the tuning parameters listed in Table 8-1 <strong>and</strong> resumes<br />

normal control action.<br />

If you want ‘Proportional only’, ‘PD’, or ‘PI’ control, you should set the Integral time<br />

parameter or derivative time parameter to OFF before commencing the tuning cycle. These<br />

parameters are found in the Loop Setup (PID) pages, see Chapter 9. The tuner will leave<br />

them off <strong>and</strong> will not calculate a value for them.<br />

8-4 Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00