<strong>2704</strong> Controller Totaliser, Timer. Clock, Counter Operation<br />

12.2.4. Minimum On Timer Mode<br />

This timer has been targeted at guaranteeing that the output remains On for a duration after<br />

the input signal has been removed. It may be used, for example, to ensure that a compressor<br />

is not cycled excessively.<br />

• The output will be set to On when the Input changes from Off to On.<br />

• When the Input changes from On to Off, the elapsed time will start incrementing towards<br />

the set Time.<br />

• The Output will remain On until the elapsed time has reached the set Time. The Output<br />

will then switch Off.<br />

• If the Input signal returns to On while the Output is On, the elapsed time will reset to 0,<br />

ready to begin incrementing when the Input switches Off.<br />

• The Triggered variable will be set while the elapsed time is >0. It will indicate that the<br />

timer is counting.<br />

Figure 12.4 illustrates the behaviour of the timer under different input conditions.<br />

Input<br />

Output<br />

Elapsed Time<br />

Triggered<br />

Time<br />

Time<br />

Figure 12-4: Minimum On Timer Under Different Input Conditions<br />