Loop Set Up<br />

<strong>2704</strong> Controller<br />

9.2.1. To Manually Set The PID And Other Tuning Parameters<br />

Do This<br />

1. From any display press<br />

as many times as necessary<br />

to access the page header<br />

menu<br />

2. Press or to select<br />

‘LP1 SETUP’<br />

This Is The Display You<br />

Should See<br />

Additional Notes<br />

Alternatives are Loop 2<br />

<strong>and</strong> Loop 3. These only<br />

appear in the list if the<br />

loops are configured.<br />

Available at L3 but may<br />

have been promoted to L1<br />

or L2.<br />

3. Press to display the<br />

sub-headers<br />

4. Press or to select<br />

PID<br />

3. Press to show the<br />

parameter list.<br />

4. Press or to<br />

choose ‘Prop B<strong>and</strong> 1’<br />

5. Press to select Prop<br />

B<strong>and</strong> 1<br />

6. Press or to set<br />

the value of the<br />

proportional b<strong>and</strong> to be<br />

stored in Set 1.<br />

R/O. PID set 1 is only<br />

displayed if gain<br />

scheduling has been<br />

enabled in configuration<br />

level.<br />

Shows the working PID<br />

set based upon PV <strong>and</strong><br />

1/2 & 2/3 boundaries.<br />

The choices are:<br />

PID Set 1<br />

PID Set 2<br />

PID Set 3<br />

The number Following<br />

‘Prop B<strong>and</strong>’ shows the<br />

gain set being edited<br />

The proportional b<strong>and</strong> can<br />

be displayed in % or in<br />

engineering units, <strong>and</strong> is<br />

adjustable between 1 <strong>and</strong><br />

9999.9.<br />

Note:<br />

Text shown in italics is user definable in configuration<br />

mode <strong>and</strong> may be different from that shown<br />

Further parameters may be<br />

set up in the same way.<br />

These are listed together<br />

with an explanation of their<br />

function in the following<br />

table<br />

…<br />

9-4 Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00