<strong>2704</strong> Controller Loop Set Up<br />

9.6. OVERRIDE CONTROL<br />

9.6.1. Introduction:<br />

Override Control allows a secondary control loop to override the main control output in order<br />

to prevent an undesirable operating condition. The override function can be configured to<br />

operate in either minimum, maximum or select mode.<br />

A typical example can be implemented in a heat treatment furnace with one thermocouple<br />

attached to the workpiece, <strong>and</strong> another situated close to the heating elements. Control of the<br />

furnace during the heating up period is regulated by the override (heating element)<br />

temperature <strong>controller</strong> which provides a safeguard against overheating. Control of the<br />

furnace will switch over to the workpiece temperature <strong>controller</strong> at some point when the<br />

temperature is near to its target setpoint. The exact point of switchover is determined<br />

automatically by the <strong>controller</strong>, <strong>and</strong> will be dependent on the selected PID terms.<br />

9.6.2. Simple Override<br />

Override control is available with analogue, time proportioning <strong>and</strong> ON/OFF control outputs.<br />

It is not available with valve position outputs. Figure 9.3 shows a simple override control<br />

loop. The main <strong>and</strong> override <strong>controller</strong> outputs are fed to a low signal selector. The override<br />

<strong>controller</strong> setpoint is set to a value somewhere above the normal operating setpoint, but<br />

below any safety interlocks.<br />

There is one Auto Manual switch for both loops. In manual mode the control outputs of both<br />

loops track the actual output therefore ensuring bumpless transfer when auto is selected.<br />

Main SP<br />

Main PV<br />

Override SP<br />

Main<br />

Control<br />

Loop<br />

Main OP<br />

Min select<br />

Control<br />

Output<br />

Override PV<br />

Override<br />

Control<br />

Loop<br />

Override OP<br />

Figure 9-3: Simple Override Control<br />

Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00 9-13