Input Operators<br />

<strong>2704</strong> Controller<br />

11. Chapter 11 Input Operators<br />

11.1. WHAT ARE INPUT OPERATORS<br />

The <strong>2704</strong> <strong>controller</strong> can have three control loops. Each loop can be independently<br />

configured to the process to be controlled. This has been described in Chapters 9 <strong>and</strong> 10 for<br />

PID, Cascade, Ratio, Override, Humidity Control, etc. It is also possible to apply custom<br />

linearisation to the inputs of each loop. This is a 16 point straight line linearisation <strong>and</strong> the<br />

parameters can be made available at Levels 1, 2 <strong>and</strong> 3 so that scaling can be carried out<br />

during commissioning.<br />

Custom linearisation is achieved under three page headers in the <strong>controller</strong>.<br />

Also included in this section are parameters which allow you to switch inputs between<br />

different thermocouple types or between a thermocouple <strong>and</strong> pyrometer when the process is a<br />

high temperature furnace.<br />

The page headers are:<br />

INPUT OPERS (Cust Lin 1<br />

Page)<br />

INPUT OPERS (Cust Lin 2<br />

Page)<br />

INPUT OPERS (Cust Lin 3<br />

Page)<br />

INPUT OPERS (Switch 1<br />

Page)<br />

INPUT OPERS (Monitor 1<br />

Page)<br />

BCD INPUT<br />

These parameters set up the custom linearisation for<br />

input 1<br />

These parameters set up the custom linearisation for<br />

input 2<br />

These parameters set up the custom linearisation for<br />

input 3<br />

These parameters provide switch over between<br />

thermocouple types or pyrometer<br />

Logs maximum <strong>and</strong> minimum, counts time above<br />

threshold<br />

To select a numerical value from an external BCD<br />

switch<br />

The Input Operators page is only available if Input Operators has been enabled in<br />

configuration level. This is described in the Engineering H<strong>and</strong>book, Part No. HA026933.<br />

Note:<br />

In addition to linearising the <strong>controller</strong> inputs channels, it is equally valid to customise other<br />

sources such as Output Channels. This allows you, for example, to compensate for non linear<br />

control valve characteristics.<br />

11-2 Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00