<strong>2704</strong> Controller Module IO<br />

18.4.7. To Calibrate the Potentiometer input<br />

The value of the potentiometer input is read by the parameter ‘Module xA Val’, where x is the<br />

number of the slot in which the Pot input module is fitted. This parameter can be scaled to<br />

read the value of the potentiometer input or as a percentage as required.<br />

To calibrate the potentiometer input:-<br />

Do This<br />

1. Access the Pot Input<br />

parameter list from the<br />

MODULE IO (Module xA)<br />

page header<br />

2. Press or to scroll<br />

to ‘Eng Val Lo<br />

This Is The Display You<br />

Should See<br />

Additional Notes<br />

This will set the minimum<br />

reading when the pot<br />

position is at minimum<br />

3. ’ Press to select ‘Eng<br />

Val Lo<br />

4. Press or to change<br />

its value<br />

5. Press to select ‘Eng<br />

Val Hi’<br />

This will set the maximum<br />

reading when the pot<br />

position is at maximum<br />

6. Press or to<br />

change its value<br />

To Calibrate the Potentiometer Minimum Position<br />

7. Press to scroll to Cal<br />

State<br />

8. Press or to<br />

select ‘Pot Low Pos’<br />

9. Adjust the potentiometer<br />

to minimum position<br />

10. To confirm, press or<br />

to select ‘Go’.<br />

(You can also select<br />

‘Abort’ at this point)<br />

To calibrate follow the<br />

instructions on the<br />

display.<br />

When the <strong>controller</strong> is<br />

calibrating the message<br />

‘Doing Fine Cal’<br />

appears.<br />

When the <strong>controller</strong> has<br />

finished the message<br />

‘Passed’ appears.<br />

Press or to<br />

‘Accept’. After 0.5 sec<br />

the display will revert to<br />

‘Idle’ completing the<br />

procedure.<br />

Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00 18-21