Logic Operators<br />

<strong>2704</strong> Controller<br />

15. Chapter 15 Logic Operators<br />

Logic Operators allow the <strong>controller</strong> to perform logical calculations on two input values.<br />

These values can be sourced from any available parameter including Analogue Values, User<br />

Values <strong>and</strong> Digital Values.<br />

The parameters to use, the type of calculation to be performed, input value inversion <strong>and</strong><br />

‘fallback’ value are determined in Configuration level (see Engineering H<strong>and</strong>book<br />

HA026933). In levels 1 to 3 you can view the values of each input <strong>and</strong> read the result of the<br />

calculation.<br />

The Logic Operators page is only available if Analogue <strong>and</strong> Logic Operators have been<br />

enabled in configuration level. This is described in the Engineering H<strong>and</strong>book.<br />

Up to 32 separate calculations can be performed <strong>and</strong> a separate page header is provided for<br />

each one.<br />

15.1.1. Logic Operations<br />

The following calculations can be performed:<br />

Off<br />

The selected logic operator is turned off<br />

AND<br />

The output result is ON when both Input 1 <strong>and</strong> Input 2 are ON<br />

OR<br />

The output result is ON when either Input 1 or Input 2 is ON<br />

XOR<br />

Exclusive OR. The output result is true when one <strong>and</strong> only one<br />

input is ON. If both inputs are ON the output is OFF.<br />

Latch<br />

The output is ON when input 1 turns ON. The output remains ON<br />

when input 1 turns OFF. The output is reset to OFF by turning<br />

input 2 ON.<br />

Equal The output result is ON when Input 1 = Input 2<br />

Greater The output result is ON when Input 1 > Input 2<br />

Less than The output result is ON when Input 1 < Input 2<br />

Greater or Equal The output result is ON when Input 1 > Input 2<br />

Less or Equal The output result is ON when Input 1 < Input 2<br />

Logic input 1<br />

Invert option<br />

Logic input 2<br />

Invert option<br />

Logic operator<br />

See 15.1.1.<br />

Output Value<br />

(result of calculation)<br />

Figure 15-1: Logic Operators<br />