<strong>2704</strong> Controller Introduction<br />

1.2. WHAT IS <strong>2704</strong><br />

The <strong>2704</strong> is a high accuracy, high stability temperature <strong>and</strong> process <strong>controller</strong> which is<br />

available in a single, dual or three loop format. It has a 120 x 160 pixel electroluminescent<br />

used to show all process information. The user interface is menu driven via the display <strong>and</strong><br />

seven front panel keys.<br />

When the <strong>2704</strong> is configured as a programmer it<br />

provides advanced programming facilities such as:<br />

• storage of up to 50 programs.<br />

• up to three variables can be profiled in each<br />

program, or one profile can be assigned to run in<br />

more than one loop.<br />

• up to sixteen event outputs can be assigned to<br />

each program.<br />

Special machine <strong>controller</strong>s can be created by<br />

connecting analogue <strong>and</strong> digital parameters to the<br />

control loops, either directly or by using a selection<br />

of mathematical <strong>and</strong> logical functions.<br />

Figure 1-1: General View of <strong>2704</strong> Controller<br />

Other features include:<br />

• A wide variety of inputs which can be configured, including thermocouples, Pt100<br />

resistance thermometers <strong>and</strong> high level process inputs.<br />

• Direct connection of zirconia oxygen probes is also supported for use in heat treatment<br />

furnaces <strong>and</strong> ceramic kiln applications.<br />

• Each loop can be defined to be PID, On/Off or motorised valve position <strong>and</strong> can control<br />

using a variety of strategies including single, cascade, override <strong>and</strong> ratio control.<br />

• PID control outputs can be relay, logic, triac or dc with motorised valve position outputs<br />

being relay triac or logic.<br />

• Auto tuning <strong>and</strong> PID gain scheduling are available to simplify commissioning <strong>and</strong><br />

optimise the process<br />

Configuration of the <strong>controller</strong> is explained in a separate Engineering Manual, Part No.<br />

HA026933. Configuration is achieved either via the front panel operator interface or by<br />

using ‘iTools’ - a configuration package which runs under the Windows 95, or NT operating<br />

systems.<br />

Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00 1-3