17.4. THE FIXED RELAY OUTPUT PARAMETERS<br />

Allows access to parameters which set up the fixed Relay output connected to terminals AA,<br />

AB <strong>and</strong> AC. This relay may be used as an alarm relay. or a time proportioning control<br />

output.<br />

17.5. TO SCALE THE FIXED RELAY OUTPUT<br />

If the relay is used as a time proportioning control output this means that the relay will, by<br />

default, be fully off for 0% power dem<strong>and</strong>, fully on for 100% power dem<strong>and</strong> <strong>and</strong> equal on/off<br />

times at 50% power dem<strong>and</strong>.<br />

As with input scaling you can change these limits to suit the process. It is important to note,<br />

however, that these limits are set to safe values for the process. For example, for a heating<br />

process it may be required to maintain a minimum level of temperature. This can be achieved<br />

by applying an offset at 0% power dem<strong>and</strong> which will maintain the relay on for a period of<br />

time. Care must be taken to ensure that this minimum on period does not cause the process to<br />

overheat<br />

These offsets can be made to parameters in the ‘AA Relay’ pages. The above example is<br />

shown in Fig 17-2<br />

PID Dem<strong>and</strong><br />

signal<br />

Eng Value Hi<br />

eg 100%<br />

Eng Value Lo<br />

eg 0%<br />

Electrical Lo<br />

eg Relay on for<br />

short period<br />

Electrical Hi<br />

eg Relay<br />

permanently on<br />

Electrical Output. In<br />

this example the<br />

on/off ratio of the<br />

output relay<br />

Table 17-2: Fixed Relay Scaling<br />

17-8 Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00