Loop Set Up<br />

<strong>2704</strong> Controller<br />

9.2.3. PID (Aux) Page<br />

Table Number:<br />

9.2.3.<br />

These parameters allow you to set up the<br />

PID sets<br />

LP1 SETUP<br />

PID(Aux) Page<br />

Parameter Name Parameter Description Value Default Access<br />

Level<br />

Active PID Set<br />

The PID set currently being<br />

used<br />

PID Set 1 to<br />

3<br />

Prop B<strong>and</strong> 1 Proportional B<strong>and</strong> Set 1 1 to 9999.9<br />

eng units<br />

Integral 1 Integral Time Set 1 Off to<br />

999.9 secs<br />

or mins<br />

Derivative 1 Derivative Time Set 1 Off to<br />

999.9 secs<br />

or mins<br />

Cutback Low 1 Cutback Low Set 1 Auto to<br />

display limit<br />

Cutback High 1 Cutback High Set 1 Auto to<br />

display limit<br />

Manual Reset 1<br />

Cool Gain 1<br />

Manual Reset Set 1 (only<br />

applies to a PD <strong>controller</strong>)<br />

Relative channel 1/channel<br />

2 Gain Set 1 (e.g. cooling.<br />

Only present if ch 1 <strong>and</strong> ch 2<br />

are in the same loop)<br />

Off, -99.9 to<br />

+100<br />

L1<br />

L1<br />

L1<br />

L1<br />

L1<br />

L1<br />

L1<br />

0.1 to 10 L1<br />

An Value 1 Analogue value 1 (see 9.2) L3<br />

The above seven parameters are repeated for set 2 <strong>and</strong> again for set 3 if the number of PID<br />

sets has been configured to 2 or 3 respectively.<br />

1/2 Boundary Sets the level at which PID<br />

set 1 changes to PID set 2<br />

Range units<br />

L3<br />

2/3 Boundary Sets the level at which PID<br />

set 1 changes to PID set 2<br />

Control Hold<br />

Aux. Control hold flag.<br />

Freezes the control output<br />

Range units<br />

No<br />

Yes<br />

Integral Hold Aux. Integral hold flag No<br />

Yes<br />

The tables in sections 9.2.2 <strong>and</strong> 9.2.3 are repeated for Loop 2 <strong>and</strong> Loop 3 if these have<br />

been configured<br />

This table does not appear if the Loop Type is Ratio.<br />

L3<br />

L3<br />

L3<br />

9-6 Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00