<strong>2704</strong> Controller Transducer Scaling<br />

19.6. TRANSDUCER SCALING PARAMETERS<br />

Table Number:<br />

18.3.1.<br />

This page shows the Transducer Scaling<br />

parameters.<br />

TXDCR SCALING<br />

(Txdcr 1)<br />

Parameter Name Parameter Description Value Default Access<br />

Level<br />

Enable Cal (1) Enable calibration Off<br />

On<br />

Off<br />

L3<br />

Start Tare (2) Start auto-tare calibration Off<br />

On<br />

Start Pnt1 Cal (3)<br />

Start Pnt2 Cal (4)<br />

Clear Cal (5)<br />

Tare Value<br />

Input Low<br />

Input High<br />

Scale Low<br />

Scale High<br />

Threshold Val (6)<br />

Shunt State (7)<br />

Cal Active<br />

Scaled Value<br />

Adjust Value<br />

OP Status<br />

Start the calibration at point<br />

1, normally the low point<br />

Start the calibration at point<br />

2, normally the low point<br />

Clear previous calibration<br />

values<br />

Sets the value that the<br />

<strong>controller</strong> will read after an<br />

auto-tare calibration<br />

Sets the scaling input low<br />

point<br />

Sets the scaling input high<br />

point<br />

Sets the scaling output low<br />

point<br />

Sets the scaling output high<br />

point<br />

The allowed difference<br />

between two consecutive<br />

averages during calibration<br />

Indicates that the shunt<br />

resistor is connected or not<br />

Indicates calibration in<br />

progress<br />

Output from the scaling<br />

block. Used for diagnostic<br />

purposes only<br />

Sets the value read by the<br />

reference source in<br />

comparison calibration only<br />

Output status based on<br />

input status <strong>and</strong> scaled PV<br />

Off<br />

On<br />

Off<br />

On<br />

Off<br />

On<br />

Display<br />

range<br />

0 - 99.999<br />

mins<br />

Off<br />

On<br />

Off<br />

On<br />

Good<br />

Bad<br />

Off<br />

Off<br />

Off<br />

Off<br />

L1<br />

L1<br />

L1<br />

L3<br />

L3<br />

L3<br />

L3<br />

L3<br />

L3<br />

L3<br />

L3 R/O<br />

L3 R/O<br />

R/O<br />

L1<br />

R/O<br />

Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00 19-13