<strong>2704</strong> Controller Totaliser, Timer. Clock, Counter Operation<br />

12.2.2. Off Delay Timer Mode<br />

This timer provides a delay between the trigger event <strong>and</strong> the Timer output. If a short pulse<br />

triggers the Timer, then a pulse of one sample time (110mS) will be generated after the delay<br />

time.<br />

• The Output is set to Off when the Input changes from Off to On.<br />

• The Output remains Off until the Time has elapsed.<br />

• If the Input returns to Off before the time has elapsed, the Timer will continue until the<br />

Elapsed Time equals the Time. It will then generate a pulse of one Sample Time<br />

duration.<br />

• Once the Time has elapsed, the Output will be set to On.<br />

• The Output will remain On until the Input is cleared to Off.<br />

• The Triggered variable will be set to On by the Input changing from Off to On. It will<br />

remain On until both the Time has elapsed <strong>and</strong> the Output has reset to Off.<br />

Figure 12.2 illustrates the behaviour of the timer under different input conditions.<br />

Input<br />

110mS<br />

Time<br />

Time<br />

Output<br />

Elapsed Time<br />

Triggered<br />

Figure 12-2: Off Delay Timer Under Different Input Conditions<br />

Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00 12-5