<strong>2704</strong> Controller Loop Set Up<br />

9.2.2. PID Page<br />

Table Number:<br />

9.2.2.<br />

These parameters allow you to set up the PID sets<br />

LP1 SETUP<br />

(PID Page)<br />

Parameter Name Parameter Description Value Default Access<br />

Level<br />

Active PID Set The PID set in current use Set 1 to 3 R/O<br />

Prop B<strong>and</strong> 1 Proportional B<strong>and</strong> Set 1 1 to 9999.9<br />

eng units<br />

Integral 1 Integral Time Set 1 Off to 999.9 L1<br />

Derivative 1 Derivative Time Set 1 secs or mins L1<br />

Cutback Low 1 Cutback Low Set 1 Auto to disp. L1<br />

Cutback High 1 Cutback High Set 1 range L1<br />

Manual Reset 1<br />

Cool Gain 1<br />

Manual Reset Set 1 (only<br />

applies to a PD <strong>controller</strong>)<br />

Relative channel 1/channel<br />

2 Gain Set 1 (e.g. cooling).<br />

Only present if ch 1 <strong>and</strong> ch 2<br />

are in the same loop<br />

Off, -99.9 to<br />

+100<br />

Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00 9-5<br />

L1<br />

L1<br />

0.1 to 10 L1<br />

An Value 1 Analogue value 1 (see 9.2) L3<br />

The above eight parameters are repeated for set 2 <strong>and</strong> again for set 3 if the number of PID<br />

sets has been configured to 2 or 3 respectively.<br />

FF Offset Feedforward Offset Value L3<br />

FF Prop B<strong>and</strong> Feedforward Proportional<br />

B<strong>and</strong>. This parameter<br />

controls the amount that the<br />

PID can affect the output<br />

L3<br />

FF Trim Limit Feedforward Trim Limit L3<br />

Remote FFwd Remote feedforward L3<br />

1/2 Boundary Sets the level at which PID<br />

set 1 changes to PID set 2<br />

2/3 Boundary Sets the level at which PID<br />

set 1 changes to PID set 2<br />

Loop Brk Time Loop break time Off<br />

On<br />

AutoDroop Comp<br />

Control Hold<br />

Manual reset when Integral<br />

turned off<br />

Control hold flag. Freezes<br />

the control output<br />

Range units<br />

Range units<br />

Manual<br />

Calc<br />

No<br />

Yes<br />

Integral Hold Integral hold flag No<br />

Yes<br />

L3<br />

L3<br />

L3<br />

L3<br />

L3<br />

L3