Programmer Operation<br />

<strong>2704</strong> Controller<br />

6.3. THE <strong>2704</strong> SETPOINT PROGRAMMER DEFINITIONS<br />

6.3.1. Run<br />

In run the programmer varies the setpoint in accordance with the profile set in the active<br />

program.<br />

6.3.2. Hold<br />

In hold the programmer is frozen at its current point. In this state you can make temporary<br />

changes to program parameters such as a target setpoint, ramp rates <strong>and</strong> dwells (if<br />

programmer configured for ramp rate) or segment duration (if programmer configured as<br />

Time to Target). Such changes will only remain effective until the end of the currently<br />

running segment, when they will be overwritten by the stored program values.<br />

6.3.3. Reset<br />

In reset the programmer is inactive <strong>and</strong> the <strong>controller</strong> behaves as a st<strong>and</strong>ard <strong>controller</strong>, with<br />

the setpoint determined by the raise/lower buttons.<br />

6.3.4. Servo<br />

When a program is run the setpoint can start from the initial <strong>controller</strong> setpoint or from the<br />

current process value. Whichever it is the starting point is called the servo point. This can be<br />

set in the program.<br />

The usual method is to servo to the process value because this will produce a smooth <strong>and</strong><br />

bumpless start to the process.<br />

If, however, when using a Ramp Rate programmer, it is essential to guarantee the time period<br />

of the first segment it may be better to set the <strong>controller</strong> to servo to setpoint. (Note: in a<br />

Time to Target programmer the segment duration will always be determined by the setting of<br />

the Segment Duration parameter.)<br />

6.3.5. Hot Start<br />

Hot start can occur in any segment type, for any PSP but is most useful to ramp segments.<br />

When run is initiated it allows the program to automatically advance to the correct point in<br />

the profile which corresponds to the operating value of the process. Hot start is enabled in<br />

configuration level <strong>and</strong> specifies which programmed variable to use when deciding the<br />

correct segment.<br />

6-4 Installation <strong>and</strong> Operation H<strong>and</strong>book. Part No HA026502 Issue 1.0 Apr-00