6-5. Method to Set Indoor Unit Function DN Code<br />

(When performing this task, be sure to use a wired remote controller.)<br />

To be performed only when system at rest<br />

1 Push the + + buttons simultaneously and hold for at<br />

least 4 seconds.<br />

The unit No. displayed first is the address of the header indoor unit in group<br />

control.<br />

Then the fan and louver of the selected indoor unit move.<br />

UNIT LOUVER<br />

2 Each time the “Select unit” side of the button is pressed,<br />

one of the indoor unit Nos. under group control is displayed in<br />

turn. Then the fan and louver of the selected indoor unit move.<br />

TEMP.<br />

TIMER SET<br />

TIME<br />

FAN<br />

SAVE<br />

ON / OFF<br />

MODE<br />

VENT<br />

3 Use the button to select the CODE No. (DN code) of the<br />

desired function.<br />

4 Use the button to select the desired SET DATA associated<br />

with the selected function.<br />

5 Push the button. (The display changes from flashing to<br />

steady.)<br />

• To change the selected indoor unit, go back to step 2.<br />

• To change the selected function, go back to step 3.<br />

3<br />

FILTER<br />

RESET TEST<br />

SET<br />

CL<br />

SWING/FIX<br />

5 4<br />

6 1 2<br />

UNIT LOUVER<br />

6 When the button is pushed, the system returns to normal off state.<br />