6-8-1. Power peak-cut Control (Standard)<br />

Header outdoor unit<br />

L1: Display lamp suring power peak cut control<br />

Locally procured<br />

Outdoor unit<br />

interface PCB<br />

Optional PCB<br />

Display<br />

relay<br />

TB1<br />

L1<br />

Power<br />

supply<br />

Operation<br />

An external power peak-cut control signal limits the peak capacity of the outdoor unit.<br />

L1: Power peak-cut control indication lamp<br />

SW1: Power peak-cut control ON switch (ON as long as target power peak-cut control has been reached or<br />

exceeded, normally OFF)*1<br />

SW2: Power peak-cut control OFF switch (OFF as long as target power peak-cut control has not been reached or<br />

exceeded, normally ON)*1<br />

*1 The inputs of SW1 and SW2 can be either pulse (100 msec or wider) or step signals.<br />

Do not turn on SW1 and SW2 simultaneously.<br />

* Be sure to provide a contact for each terminal.<br />

Power peak-cut control settings<br />

Power peak-cut control P.C.<br />

board<br />

Power peak-cut control ON<br />

signal received<br />

Power peak-cut control OFF<br />

signal received<br />

CN513<br />

SW07<br />

ON<br />

OFF<br />

1 2 3 4<br />

Bit 2 OFF<br />

Connection cable<br />

SW1 SW2 L1<br />

[OPERATION]<br />

PJ17 TB2<br />

COM<br />

ON<br />

[ON]<br />

COM<br />

OFF<br />

[OFF]<br />

Interface P.C. board of header outdoor unit<br />

SW07 Bit 1 OFF<br />

SW07 Bit 1 ON<br />

ON OFF ON 0% (forced stop) 60% capacity (upper limit regulated)<br />

OFF ON OFF 100% (normal operation) 100% (normal operation)<br />

Two-core cable support <br />

SMMS-i models allows ON/OFF power peak-cut control to be implemented using a power peak-cut control ON<br />

input (SW1) alone, provided that the J16 jumper wire on the interface P.C. board of the header outdoor unit has<br />

been removed.<br />

Shield<br />

wire<br />

SW1<br />

SW2<br />

SW1<br />

SW2<br />

Shield<br />

wire<br />

For SW1 and SW2, be sure to provide novoltage<br />

contacts for each terminal.<br />

The input signals of SW1 and SW2 may be pulse<br />

input (100 msec or more) or continuous make.<br />

Header outdoor unit<br />

L1: Display lamp suring power peak cut control<br />

Locally procured<br />

Outdoor unit<br />

interface PCB<br />

Optional PCB<br />

Display<br />

relay<br />

TB1<br />

L1<br />

Power<br />

supply<br />

J16 Cut<br />

SW07<br />

ON<br />

OFF<br />

1 2 3 4<br />

Bit 2 ON<br />

CN513<br />

[OPERATION]<br />

PJ17 TB2<br />

COM<br />

ON<br />

[ON]<br />

COM<br />

OFF<br />

[OFF]<br />

Shield wire<br />

Shield wire<br />

SW1<br />

Connection cable<br />