(8) Set Bits 1 and 2 of SW30 on the interface P.C. board same as that of the failed header unit (terminator<br />

resistance setting).<br />

Outdoor interface P.C. board of unit selected as new header unit<br />

(7)<br />

Turn on Bit 2 of SW09.<br />

SW06 SW07 SW09 SW10<br />

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />

SW11<br />

SW12<br />

SW13<br />

SW14<br />

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />

SW16<br />

SW17<br />

1 2 3 4 1 2 3 4<br />

(6)<br />

Set SW13 and SW14<br />

identically to failed header unit.<br />

(8)<br />

Set Bits 1 and 2 of SW30<br />

identically to failed header unit.<br />

[Wiring changes to communication line]<br />

(9) Redirect the indoor-outdoor communication line connected to the failed header unit [U1/U2] to the unit selected<br />

as the header unit [U1/U2].<br />

(10)If a central control device is connected, connect the central control communication line [U3/U4] to the<br />

communication line terminal of the unit selected as the new header unit [U3/U4], and connect up the tie<br />

connector between the [U1/U2] and [U3/U4] terminals.<br />

Failed header unit<br />

Unit selected as new header unit<br />

(previously follower unit No. 1)<br />

Follower unit No. 2<br />

Outdoor-outdoor communication line (U5/U6)<br />

Central control communication line<br />

(U3/U4 terminal)<br />

Outdoor-outdoor communication line<br />

(U1/U2 terminal)<br />

(9)<br />

Redirect the indoor-outdoor communication<br />

line from failed header unit to unit selected<br />

as header unit [U1/U2].<br />

(10)<br />

If central control device is connected, redirect central<br />

control communication line from failed header unit to<br />

unit selected as new header unit [U3/U4].<br />

(11)Turn on the power supply to all the units connected to the system other than the failed unit.<br />

Determine what to do with the power supply to the failed unit in the following manner.<br />

<br />

Leave the power supply off.<br />

<br />

Turn on the power supply to protect the compressor (by turning on the case heater).<br />

(When the power supply to the unit is turned on, [E19] (error in the number of outdoor header units) will be<br />

displayed on the 7-segment display. However, this will not cause any problems.)<br />

This is the end of header outdoor unit backup operation setting. Check the operation.<br />