Procedure 3: Writing Setting Data in EEPROM<br />

(The EEPROM of the service P.C. board has been set to the factory default values.)<br />

1 Push the + + buttons simultaneously and hold for at least 4 seconds. 1 (This number<br />

corresponds to the same number shown on the Remote Controller Operation Diagram.)<br />

(Under UNIT No., ALL is displayed.)<br />

At the same time, the CODE No. (DN code) 10 is displayed, and the fan of the indoor unit comes on, with the<br />

louver swinging, depending on the model.<br />

2 The button allows you to moved the CODE No. (DN code) up/down by one place. 3<br />

3 First, set the type and capacity codes of the indoor unit.<br />

(Changing the type and capacity codes in EEPROM overwrites the factory default settings.)<br />

(1) Set the CODE No. (DN code) to 10 (no change)<br />

(2) Use the button to select the type. 4<br />

(For example, 0001 is for the 4-way air discharge cassette type.) - See the CODE No. list.<br />

(3) Push the button. (The display should change from flashing to steady.) 5<br />

(4) Use the button to set the CODE No. (DN code) to 11.<br />

(5) Use the button to set the capacity code.<br />

(For example, 0012 is for the 027 type.) - See the CODE No. list.<br />

(6) Push the button. (The display should change from flashing to steady.)<br />

* Setting 4-way Air Discharge Cassette indoor unit model only<br />

(7) Using the set temperature / buttons, set “ ” to the CODE No. (DN code).<br />

(8) Using the timer time / buttons, set the dat. (0001)<br />

(9) Push button (The setting completes if the setting data are displayed.)<br />

(10)Push the button to bring the system back to normal off state. 6<br />

4 Next, write any setting changes made on-site after installation, such as address settings, in the<br />

EEPROM. Perform the tasks specified in step 1 again.<br />

5 Use the button to set the CODE No. (DN code) to 01 (To set filter sign lighting time)<br />

6 Check the value displayed with the value jotted down in Procedure 1 and information proved by<br />

the customer.<br />

(1) If there is a discrepancy, change the setting in accordance with the jotted-down value, and push the button.<br />

(The display should change from flashing to steady.)<br />

(2) If there is no discrepancy, do nothing.<br />

7 Use the button to change the CODE No. (DN code).<br />

Again, check the value, and change the setting if necessary.<br />

8 Repeat steps 6 and 7 until all the settings are checked.<br />

9 When finished, push the button to bring the system back to normal off state. 6<br />

In the case of group operation, turn the unit off, reconnect the indoor-indoor group control wiring and CN41<br />

connectors, and turn on all the indoor units.<br />

(It takes the system about 1 minute to become responsive to remote controller operation.)<br />

* CODE No. (DN code) go from 01 to FF with a few gaps along the way.<br />

If you realize you have wrongly corrected a certain setting after pushing the button, you can recover the initial<br />

value by pushing the button, provided that the CODE No. (DN code) is yet to be changed.<br />