NOTE<br />

(1) When setting the line address from the remote controller, do not use addresses 29 and 30.<br />

Addresses 29 and 30 cannot be set up on the outdoor unit. If they are incorrectly used, the code “E04” (indoor/outdoor<br />

communication circuit error) is output.<br />

(2) When manual address setup has been done from a remote controller, and central control over refrigerant lines is to be done,<br />

setup the header unit of each line as follows:<br />

• Using SW13 and SW14 on the interface PC board of the header unit of each line, setup the line address for each<br />

line.<br />

• Except for the line with the smallest line address number, set SW03-bit 2 to “off” for the interface PC board of the<br />

header unit of lines connected to the same central control (put the resistance of the end terminals of the central<br />

control line, indoors and outdoors, into one).<br />

• Connect the relay connector between U1/U2 and U3/U4 of the header unit for each refrigerant line.<br />

• After that, set up the central control address. (For central control address setup, refer to the installation manual of<br />

the central control devices.)<br />

Confirming the indoor unit addresses and the position of an<br />

indoor unit using the remote controller<br />

◆Confirming the numbers and positions of indoor units<br />

To see the indoor unit address of an indoor unit which you know the position of<br />

▼ When the unit is individual (the indoor unit is paired with a wired remote controller one-to-one), or<br />

it is a group-controlled one.<br />

CODE No.<br />

UNIT No.<br />

TEMP.<br />

TIMER SET<br />

TIME<br />

ON / OFF<br />

1<br />

Starts<br />

running<br />

FILTER<br />

RESET TEST<br />

SET<br />

CL<br />

2<br />

(Execute it while the units are running.)<br />

1 Push the button if the units stop.<br />

2<br />

UNIT LOUVER<br />

Push the button (left side of the button).<br />

A unit numbers is indicated on the LCD (it will disappear after a few seconds). The indicated number<br />

shows the system address and indoor unit address of the unit.<br />

When 2 or more indoor units are connected to the remote controller (group-controlled units), a number of other<br />

UNIT LOUVER<br />

connected units appears each time you push the button (left side of the button).<br />

131