▼ Ventilating fan control from remote controller<br />

[Function]<br />

• The start/stop operation can be operated from the wired remote controller when air to air heat exchanger or<br />

ventilating fan is installed in the system.<br />

• The fan can be operated even if the indoor unit is not operating.<br />

• Use a fan which can receive the no-voltage A contact as an outside input signal.<br />

• In a group control, the units are collectively operated and they can not be individually operated.<br />

1. Operation<br />

Handle a wired remote controller in the following procedure.<br />

* Use the wired remote controller during stop of the system.<br />

* Be sure to set up the wired remote controller to the header unit. (Same in group control)<br />

* In a group control, if the wired remote controller is set up to the header unit, both header and follower units<br />

are simultaneously operable.<br />

1 Push concurrently + + buttons for 4 seconds or more.<br />

The unit No. displayed firstly indicates the header indoor unit address in the group control.<br />

In this time, the fan of the selected indoor unit turns on.<br />

2<br />

UNIT LOUVER<br />

Every pushing button, the indoor unit numbers in group control are displayed<br />

successively.<br />

In this time, the fan of the selected indoor unit only turns on.<br />

3 Using the setup temp or button, specify the CODE No. 31.<br />

4 Using the timer time or button, select the SET DATA. (At shipment: )<br />

The setup data are as follows:<br />

SET DATA<br />

Handling of operation of air to air heat exchanger or ventilating fan<br />

Unavailable (At shipment)<br />

Available<br />

5 Push button. (OK if display goes on.)<br />

• To change the selected indoor unit, go to the procedure 2 ).<br />

• To change the item to be set up, go to the procedure 3 ).<br />

6 Pushing returns the status to the usual stop status.<br />

2. Wiring<br />

CN32<br />

FAN DRIVE<br />

(2P WHI)<br />

1<br />

2<br />

Indoor control<br />

P.C. board<br />

1<br />

2<br />

Relay (DC12V, procured locally)<br />

Corresponds to the relay up<br />

to one that the rated current<br />

of the operation coil is approx. 75mA<br />

Outside control<br />

input of fan<br />

To terminal<br />

Note) Determine the cable length between the indoor<br />

control P.C. board and the relay within 2m.<br />

Compact 4-way Air Discharge Cassette type<br />

4-way Air Discharge Cassette type<br />

1-way Air Discharge Cassette type (2 series)<br />

Concealed Duct Standard type<br />

model :<br />

Slim Duct type<br />

Under Ceiling type<br />

High Wall type<br />

Corresponds up to a relay in which rated current of<br />

the operation coil is approx. 75mA<br />

Other type models:<br />

Correspond up to a relay in which rated current of the<br />

operation coil is approx. 16mA (Does not correspond to a<br />

terminal block type relay on the market.)<br />

104